REYRY

Instrumentation cables are suitable for
industrial control system as needed in
measurement, control, signalling and
data system technology.

Special Features on Request :
• Fire Resistance
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Heat Resistance
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen
• Nylon Coated


Note :
Conductor Shape
All construction supplied in solid (re) or non compacted circular stranded (rm)

Standard Packing
Size 1.5 mm² :
1 - 30 pairs supplied in wooden drum @ 1000 m
36 - 50 pairs supplied in wooden drum on available length
Size 2.5 mm² :
1 - 20 pairs supplied in wooden drum @ 1000 m
24 - 50 pairs supplied in wooden drum on available length
Length tolerance per drum ± 2%
Size of drain wire : 0.5 mm²

No.
of
pairs
Size
1.5 mm2
2.5 mm2
Overall
Diameter

Cable
Weight
Overall
Diameter
Cable
Weight
approx.
approx. approx. approx.
mm
kg/km
mm
kg/km
1 12.7 306 15.1 421
2 15.5 419 19.1 669
3 19.1 645 22.0 805
4 21.0 739 24.5 1,076
5 22.5 849 26.5 1,251
6 25.0 1,090 28.0 1,369
7 26.0 1,172 29.5 1,491
9 28.0 1,352 33.0 1,803
10 29.0 1,425 35.5 2,159
12 31.5 1,639 37.5 2,412
14 33.0 1,799 40.0 2,678
15 33.5 1,889 41.0 2,867
16 34.5 1,975 42.0 2,978
18 36.0 2,114 44.5 3,227
19 37.0 2,184 45.5 3,337
20 37.5 2,303 48.0 3,962
24 41.5 2,858 51.5 4,412
30 44.5 3,272 56.5 5,210
36 50.5 4,278 61.0 5,898
40 52.5 4,566 63.5 6,378
48 56.0 5,136 68.5 7,296
50 56.5 5,238 69.5 7,500

 

Conductor Insulation Mutual
Capacitance
AC
Voltage
Test
Nominal
Cross
Section
Resistance
at 20°C
Resistance
at 20°C
  max.
min. max. -
mm2 ohm/km M.ohm.km pF/m volt/1 min
  1 Pair ≥ 2 Pair  
1.5 12.1 12.3 25 250 1000
2.5 7.41 7.56 25 250 1000