REYKRY

Instrumentation cables are suitable for
industrial control system as needed in
measurement, control, signalling and
data system technology.

Special Features on Request :
• Fire Resistance
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Heat Resistance
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen
• Nylon Coated


Note :
Conductor Shape
All construction supplied in solid (re) or non compacted circular stranded (rm)

Standard Packing
Size 1.5 mm² :
1 - 24 pairs supplied in wooden drum @ 1000 m
30 - 50 pairs supplied in wooden drum on available length
Size 2.5 mm² :
1 - 15 pairs supplied in wooden drum @ 1000 m
16 - 50 pairs supplied in wooden drum on available length
Length tolerance per drum ± 2%
Size of drain wire : 0.5 mm²

No.
of
pairs
Size
1.5 mm2
2.5 mm2
Overall
Diameter

Cable
Weight
Overall
Diameter
Cable
Weight
approx.
approx. approx. approx.
mm
kg/km
mm
kg/km
1 18.1 955 19.9 1,136
2 21.0 1,180 24.5 1,569
3 23.5 1,477 26.5 1,818
4 25.0 1,657 29.0 2,154
5 26.5 1,829 31.0 2,429
6 28.0 1,978 33.0 2,729
7 29.0 2,108 35.5 3,158
9 32.0 2,549 40.0 3,917
10 33.0 2,699 41.0 4,149
12 35.5 3,189 43.5 4,542
14 38.0 3,543 47.5 5,466
15 39.0 3,775 49.0 5,837
16 40.0 3,995 50.0 6,027
18 41.5 4,239 52.5 6,495
19 42.5 4,357 53.5 6,680
20 43.5 4,513 55.0 7,087
24 48.0 5,521 59.0 8,040
30 52.0 6,424 64.5 9,419
36 56.0 7,312 69.5 10,901
40 58.0 7,949 72.0 11,598
48 63.0 9,070 79.0 14,232
50 63.5 9,276 80.0 14,562

 

Conductor Insulation Mutual
Capacitance
AC
Voltage
Test
Nominal
Cross
Section
Resistance
at 20°C
Resistance
at 20°C
  max.
min. max. -
mm2 ohm/km M.ohm.km pF/m volt/1 min
  1 Pair ≥ 2 Pair  
1.5 12.1 12.3 25 250 1000
2.5 7.41 7.56 25 250 1000