ACSR
Aluminium Conductor Galvanized Steel Reinforced
Standard Specification : BS 215 Part 2 : 1970
| Type | Number / Diameter of Wire |
Calculated Cross Section Area |
Approx. Overall Diameter |
Approx. Weight of Conductor |
Calculated Breaking Load |
DC Resistance at 20° C Max. |
Current Carrying Capacity * |
Standard Length per Reel |
||
| AL | GSW | AL | GSW | |||||||
|
No. / mm
|
No. / mm |
mm²
|
mm² |
mm
|
kg/km
|
kN | Ohm/km | A | m | |
| Gopher | 6 / 2.36 | 1 / 2.36 | 26.2 | 4.4 | 7.08 | 106 | 9.61 | 1.093 | 153 | 2,000 |
| Weasel | 6 / 2.59 | 1 / 2.59 | 31.6 | 5.3 | 7.77 | 128 | 11.45 | 0.9077 | 173 | 2,000 |
| Ferret | 6 / 3.00 | 1 / 3.00 | 42.4 | 7.1 | 9.00 | 171 | 15.20 | 0.6767 | 208 | 2,000 |
| Rabbit | 6 / 3.35 | 1 / 3.35 | 52.9 | 8.8 | 10.05 | 214 | 18.35 | 0.5426 | 240 | 2,000 |
| Horse | 12 / 2.79 | 7 / 2.79 | 73.4 | 42.8 | 13.95 | 538 | 61.20 | 0.3936 | 308 | 2,000 |
| Dog | 6 / 4.72 | 7 / 1.57 | 105.0 | 13.6 | 14.15 | 394 | 32.70 | 0.2733 | 371 | 2,000 |
| Wolf | 30 / 2.59 | 7 / 2.59 | 158.1 | 36.9 | 18.13 | 725 | 69.20 | 0.1828 | 487 | 2,000 |
| Dingo | 18 / 3.35 | 1 / 3.35 | 158.7 | 8.8 | 16.75 | 505 | 35.70 | 0.1815 | 478 | 2,000 |
| Lynx | 30 / 2.79 | 7 / 2.79 | 183.4 | 42.8 | 19.53 | 842 | 79.80 | 0.1576 | 536 | 2,000 |
| Caracal | 18 / 3.61 | 1 / 3.61 | 184.2 | 10.2 | 18.05 | 587 | 41.10 | 0.1563 | 526 | 2,000 |
| Panther | 30 / 3.00 | 7 / 3.00 | 212.1 | 49.5 | 21.00 | 973 | 92.25 | 0.1363 | 588 | 2,000 |
| Jaguar | 18 / 3.86 | 1 / 3.86 | 210.6 | 11.7 | 19.30 | 671 | 46.55 | 0.1367 | 573 | 2,000 |
| Zebra | 54 / 3.18 | 7 / 3.18 | 428.9 | 55.6 | 28.62 | 1,620 | 131.90 | 0.0674 | 911 | 2,000 |
| *Note : | |||
| Ambient temperature |
: 35°C | Conductivity of Al | : 61 % IACS |
| wind velocity | : 0.6 m/sec | Solar absorbtion coeffcient | : 0.5 |
| Continuous operating temperature of conductor | : 80°C | Emissivity with respect to black body | : 0.6 |