ACSR
Aluminium Conductor Galvanized Steel Reinforced
Standard Specification : DIN EN 50182 : 2001
| Size | Number / Diameter of Wire |
Calculated Cross Section Area |
Approx. Overall Diameter |
Approx. Weight of Conductor |
Calculated Breaking Load |
DC Resistance at 20° C Max. |
Current Carrying Capacity * |
Standard Length per Reel |
||
| AL | GSW | AL | GSW | |||||||
| mm² |
No. / mm
|
No. / mm |
mm²
|
mm² |
mm
|
kg/km
|
kN | Ohm/km | A | m |
| 35/6 | 6 / 2.70 | 1 / 2.70 | 34.4 | 5.7 | 8.10 | 139 | 12.37 | 0.8342 | 180 | 2,000 |
| 50/8 | 6 / 3.20 | 1 / 3.20 | 48.3 | 8.0 | 9.60 | 195 | 16.81 | 0.5939 | 220 | 2,000 |
| 70/12 | 26 / 1.85 | 7 / 1.44 | 69.9 | 11.4 | 11.72 | 282 | 26.27 | 0.4132 | 290 | 2,000 |
| 94/22 | 30 / 2.00 | 7 / 2.00 | 94.2 | 22.0 | 14.00 | 432 | 43.17 | 0.3067 | 350 | 2,000 |
| 95/15 | 26 / 2.15 | 7 / 1.67 | 94.4 | 15.3 | 13.61 | 380 | 34.93 | 0.3060 | 350 | 2,000 |
| 95/34 | 36 / 1.85 | 7 / 2.50 | 96.8 | 34.4 | 14.90 | 537 | 57.07 | 0.2990 | 360 | 2,000 |
| 120/20 | 26 / 2.44 | 7 / 1.90 | 121.6 | 19.8 | 15.46 | 491 | 44.50 | 0.2376 | 410 | 2,000 |
| 120/42 | 36 / 2.05 | 7 / 2.75 | 118.8 | 41.6 | 16.45 | 654 | 68.79 | 0.2435 | 415 | 2,000 |
| 125/30 | 30 / 2.33 | 7 / 2.33 | 127.9 | 29.8 | 16.31 | 587 | 56.41 | 0.2260 | 425 | 2,000 |
| 150/25 | 26 / 2.70 | 7 / 2.10 | 148.9 | 24.2 | 17.10 | 601 | 53.67 | 0.1940 | 470 | 2,000 |
| 150/53 | 36 / 2.30 | 7 / 3.10 | 149.6 | 52.8 | 18.50 | 827 | 84.29 | 0.1934 | 480 | 2,000 |
| 170/40 | 30 / 2.70 | 7 / 2.70 | 171.8 | 40.1 | 18.90 | 788 | 74.89 | 0.1683 | 515 | 2,000 |
| 185/30 | 26 / 3.00 | 7 / 2.33 | 183.8 | 29.8 | 18.99 | 741 | 65.27 | 0.1571 | 535 | 2,000 |
| 210/35 | 26 / 3.20 | 7 / 2.49 | 209.1 | 34.1 | 20.27 | 844 | 73.36 | 0.1381 | 590 | 2,000 |
| 210/50 | 30 / 3.00 | 7 / 3.00 | 212.1 | 49.5 | 21.00 | 973 | 92.46 | 0.1363 | 610 | 2,000 |
| 240/40 | 26 / 3.45 | 7 / 2.68 | 243.1 | 39.5 | 21.84 | 980 | 85.12 | 0.1188 | 640 | 2,000 |
| 240/80 | 36 / 2.90 | 19 / 2.35 | 237.8 | 82.4 | 23.35 | 1,305 | 134.37 | 0.1218 | 645 | 2,000 |
| 257/60 | 30 / 3.30 | 7 / 3.30 | 256.6 | 59.9 | 23.10 | 1,177 | 108.20 | 0.1126 | 665 | 2,000 |
| 300/50 | 26 / 3.86 | 7 / 3.00 | 304.3 | 49.5 | 24.44 | 1,227 | 105.09 | 0.0949 | 740 | 2,000 |
| 40/110 | 78 / 2.36 | 19 / 2.70 | 341.2 | 108.8 | 22.94 | 1,797 | 183.73 | 0.0848 | 800 | 2,000 |
| 380/50 | 54 / 3.00 | 7 / 3.00 | 381.7 | 49.5 | 27.00 | 1,442 | 121.30 | 0.0758 | 840 | 2,000 |
| 450/40 | 48 / 3.45 | 7 / 2.68 | 448.7 | 39.5 | 28.74 | 1,548 | 119.05 | 0.0644 | 920 | 2,000 |
| 560/50 | 48 / 3.86 | 7 / 3.00 | 561.7 | 49.5 | 32.16 | 1,938 | 146.28 | 0.0515 | 1,040 | 2,000 |
| 635/117 | 38 / 3.25 22 / 4.30 |
19 / 2.80 | 634.7 | 117.0 | 35.60 | 2,669 | 236.50 | 0.0455 | 1,106 | 2,000 |
| 680/85 | 54 / 4.00 | 19 / 2.40 | 678.6 | 86.0 | 36.00 | 2,548 | 206.56 | 0.0426 | 1,150 | 2,000 |
| 1280/183 | 100 / 4.05 | 19 / 3.50 | 1288.2 | 182.8 | 49.90 | 4,998 | 407.20 | 0.0225 | 1,780 | 1,000 |
| *Note : | |||
| Ambient temperature |
: 35°C | Continuous operating temperature of conductor | : 80°C |
| wind velocity | : 0.6 m/sec | Conductivity of Al | : 61 % IACS |